120KVA DPH GEN2 Delta UPS
KSh 1,350,000.00
+254 (0) 111 053-530 |+254717492458
Description
DPH GEN2 120KVA Delta UPS
Technical Specifications
Model
DPH-120K
Power Rating
120 kVA/kW
20 kW Power Module Quantity: Up to 6 units
Input
Nominal Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Range: 305~478 Vac (full load), 228~478 Vac (70% load)
Current Harmonic Distortion: ≤ 2% *
Power Factor: > 0.99
Frequency Range: 50/60 Hz
Output
Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion: ≤ 1% (linear load); ≤ 4% (non-linear load)
Voltage Regulation: ± 1% (static)
Frequency: 50/60 Hz
Overload Capability: ≤ 125%: 10 minutes; ≤ 150%: 1 minute; > 150%: 1 second
Display: 10” color touch screen
Interface
Standard
External battery temperature detection x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2; Type B x 1), RS232 Port x 1, Modbus Port x 1, BMS (RJ45) x 1, Ethernet x 1, SNMP Slot x 1, REPO Port x 1
Conformance
Safety: CE
Efficiency
AC-AC: > 96% (Peak efficiency)
ECO Mode: 99%
Battery
Nominal Voltage: ± 240 Vdc (default, ± 180 Vdc ~ ± 276 Vdc configurable)
Charge Voltage: ± 272 Vdc (adjustable from 204 V to 312 V)
Protection of Battery Deep Discharge: Yes
Environment
Operating Temperature: 0~40℃
Relative Humidity: 95% (non-condensing)
Audible Noise (at one meter): < 65 dB
IP Protection: IP20
Others
Parallel Redundancy and Expansion: Module and system redundancy, Maximum 8 units
Battery Start: Yes
Physical
Dimensions (W x D x H): 600 x 850 x 1445 mm
Weight – UPS System (without power modules)
162 kg
Weight – 20 kW Power Module (optional): 18 kg
DPH Series Documents